Warning 3P HV W3

Grid_phase_wrong

Incorrect grid phase sequence

Academy field checklist (Grid_phase_wrong) — no EcoBSS service-table row for this bit.

Register map

Family
Three-phase HV
Register
553
Bit
2

Field checks

  1. On three-phase GRID, swap any two phases (L1↔L2 or L2↔L3) and re-check rotation.
  2. Do not enable export until phase sequence is correct.
  3. Contact Inversol if the fault returns after a clean power cycle.

FAQ

What does EcoBSS W3 mean?
Incorrect grid phase sequence
What should I check for EcoBSS W3?
  1. On three-phase GRID, swap any two phases (L1↔L2 or L2↔L3) and re-check rotation.
  2. Do not enable export until phase sequence is correct.
  3. Contact Inversol if the fault returns after a clean power cycle.
When should I contact Inversol?
Confirm LV vs HV family on the nameplate, complete the field checks, then contact Inversol with model, SN, family, and a photo if the code returns after a clean power cycle.

Partner lookup from EcoBSS Flex register map V1.2 — not a substitute for the official service manual or live measurements. Always match the inverter family (3P LV / FLEX 3L vs 3P HV).