Skip to content

Partner Academy · Error codes

EcoBSS

EcoBSS / FLEX warnings & faults

Register bit maps for EcoBSS Flex hybrids: three-phase LV (FLEX 3L) and three-phase HV. Match the code on the display to the correct family tab.

← All brands

Source: EcoBSS Flex register map V1.2. System names match the English token in the vendor bit list. The same Fn/Wn can differ between 3P LV (FLEX 3L) and 3P HV — pick the family tab that matches the inverter.

Error won't clear? Send a photo of the display to WhatsApp +995 568 999 668: an Inversol engineer will tell you what to check.

EcoBSS three-phase LV / FLEX 3L class — same code number can differ from the HV map.

W Warnings

Code Bit System name Description
W1 0 reserve Reserved / unused warning bit
Field checks
  1. Reserved bit — usually ignore unless the logger shows it stuck with a real fault.
  2. Capture model, SN, family, and a screenshot before escalating.
  3. Contact Inversol if the fault returns after a clean power cycle.
W2 1 Fan_Warn Cooling fan warning
Field checks
  1. Check that cooling fans spin freely and intake/exhaust are not blocked by dust.
  2. If blades are free but the fan stays off, plan a fan-module replacement.
  3. Contact Inversol if the fault returns after a clean power cycle.
W3 2 Grid_phase_wrong Incorrect grid phase sequence
Field checks
  1. On three-phase GRID, swap any two phases (L1↔L2 or L2↔L3) and re-check rotation.
  2. Do not enable export until phase sequence is correct.
  3. Contact Inversol if the fault returns after a clean power cycle.
W4 3 meter_Comm_Fail Energy meter communication failure
Field checks
  1. Check RS485 / meter wiring, baud rate, and Modbus address vs the external meter (e.g. Eastron).
  2. Confirm CT orientation and that the meter is powered.
  3. Contact Inversol if the fault returns after a clean power cycle.
W12 11 Grid_TypeWrong Wrong grid type setting
Field checks
  1. Open grid settings and confirm grid type / frequency match the site (e.g. 50 Hz EU).
  2. After correcting, restart AC/DC cleanly.
  3. Contact Inversol if the fault returns after a clean power cycle.
W31 14 Battery_comm_warn Energy storage communication warning
Field checks
  1. Check CAN/RS485 to the energy storage, DIP addresses, and that BMS is awake.
  2. Verify cable integrity and termination on long runs.
  3. Contact Inversol if the fault returns after a clean power cycle.
W32 15 Parallel_information_lose Parallel sync signal lost
Field checks
  1. In a cluster, check Parallel A/B / sync cables and Master–Slave addressing.
  2. Power units in the documented order; a transient W32 at start can clear when all go ON.
  3. Contact Inversol if the fault returns after a clean power cycle.

F Faults (F1–F64)

Code Bit System name Description
F1 0 DC_InversedFailure Reverse DC (PV) polarity fault
Field checks
  1. Check PV input polarity (and DC string polarity).
  2. Contact Inversol if the unit does not return to normal after correcting polarity.
F2 1 DC_Insulation_Failure DC insulation resistance permanent fault
Field checks
  1. Measure PV/DC insulation to earth (megger); look for damaged cable or wet MC4s.
  2. Do not raise trip thresholds to hide a real earth fault.
  3. Isolate strings one by one to find the weak string.
  4. Contact Inversol if the fault returns after a clean power cycle.
F3 2 GFDI_Failure DC leakage / GFDI fault
Field checks
  1. Disconnect PV, verify PE earth continuity, then restart.
  2. If it returns, check the leakage/GFDI sensor path and cable sheath damage.
  3. Contact Inversol if the fault returns after a clean power cycle.
F4 3 GFDI_Ground_Failure Ground / GFDI fault
Field checks
  1. Same GFDI path as F3: PE bond, PV isolation, leakage sensor.
  2. Clear moisture / damaged insulation before returning to service.
  3. Contact Inversol if the fault returns after a clean power cycle.
F5 4 EEPROM_Read_Failure EEPROM read failure
Field checks
  1. Try a clean AC/DC restart, then factory-reset only if you can restore site settings afterward.
  2. Persistent F5 usually means control-board service — escalate with SN and photo.
  3. Contact Inversol if the fault returns after a clean power cycle.
F6 5 EEPROM_Write_Failure EEPROM write failure
Field checks
  1. EEPROM write failed — retry after clean restart; avoid power loss mid-save.
  2. Persistent write faults need control-board service.
  3. Contact Inversol if the fault returns after a clean power cycle.
F7 6 DC/DC_Softstart_Fault DC/DC soft-start fault
Field checks
  1. BUS voltage cannot be established from PV or from energy storage.
  2. Restart the inverter; if the fault remains, contact Inversol.
F8 7 GFDI_Relay_Failure GFDI relay / contactor fault
Field checks
  1. Check GFDI / safety contactor feedback wiring and that the contactor actuates.
  2. Do not bypass safety relays.
  3. Contact Inversol if the fault returns after a clean power cycle.
F9 8 IGBT_Failure IGBT power module failure
Field checks
  1. Stop the plant; do not repeatedly restart into a hard IGBT fault.
  2. Record bus voltage, load, and mode at trip — escalate for power-module diagnosis.
  3. Contact Inversol if the fault returns after a clean power cycle.
F10 9 AuxPowerBoard_Failure Auxiliary power board failure
Field checks
  1. Confirm auxiliary supply fuses / connectors seated; look for burned smell on the aux board.
  2. Escalate for board-level service if it returns immediately.
  3. Contact Inversol if the fault returns after a clean power cycle.
F11 10 AC_MainContactor_Failure AC main contactor failure
Field checks
  1. Check main AC contactor coil voltage, feedback contacts, and mechanical free travel.
  2. Inspect for welded contacts after a heavy fault.
  3. Contact Inversol if the fault returns after a clean power cycle.
F12 11 AC_SlaveContactor_Failure AC auxiliary contactor failure
Field checks
  1. Check auxiliary / bypass contactor wiring and feedback the same way as the main contactor.
  2. Confirm the control sequence is not commanding an impossible state.
  3. Contact Inversol if the fault returns after a clean power cycle.
F13 12 Working_mode_change Grid / working mode changed
Field checks
  1. F13 can appear when grid type or frequency settings change.
  2. F13 can appear when energy-storage mode is set to “No battery / no storage”.
  3. On older firmware, F13 may appear when the system working mode changes.
  4. Usually F13 clears automatically.
  5. If it persists: turn off DC and AC switches, wait one minute, turn them on again.
  6. Contact Inversol if the fault does not clear.
F14 13 DC_OverCurr_Fault DC software overcurrent fault
F15 14 SW_AC_OverCurr_Fault AC software overcurrent fault
Field checks
  1. Check that emergency (UPS) and common loads are within the allowed power range.
  2. Restart and verify correct operation.
  3. Contact Inversol if the fault does not clear.
F16 15 GFCI_Failure GFCI (RCD) AC leakage fault
Field checks
  1. Check PV-side cable earthing / insulation to earth.
  2. Restart the system 2–3 times.
  3. If the fault remains, contact Inversol.
F17 0 Tz_PV_OverCurr_Fault PV overcurrent fault
Field checks
  1. Check PV string current vs MPPT rating; look for reverse current or damaged modules.
  2. Verify polarity and string configuration before restart.
  3. Contact Inversol if the fault returns after a clean power cycle.
F18 1 HW_Ac_OverCurr_Fault Hardware AC overcurrent fault
Field checks
  1. Check that emergency and common loads are within range.
  2. Restart and verify operation.
  3. Contact Inversol if the problem repeats.
F19 2 Tz_Integ_Fault Hardware integration / MCU fault
Field checks
  1. Clean power cycle once; if F19 returns immediately, treat as MCU / hardware integration — escalate, do not keep cycling.
  2. Contact Inversol if the fault returns after a clean power cycle.
F20 3 Tz_Dc_OverCurr_Fault DC hardware overcurrent fault
Field checks
  1. Check PV module and energy-storage connections.
  2. In off-grid mode, starting into a large load can trigger F20 — reduce the load.
  3. Turn off DC and AC switches, wait one minute, then turn them on again.
  4. Contact Inversol if the fault does not clear.
F21 4 Tz_HV_OverCurr_Fault DC bus / HV overcurrent fault
Field checks
  1. Check PV input current and energy-storage charge/discharge current settings.
  2. Restart the system 2–3 times.
  3. If the fault persists, contact Inversol.
F22 5 Tz_EmergStop_Fault Emergency stop / grid disconnect fault
Field checks
  1. Confirms the inverter was shut down remotely (or via emergency-stop path).
  2. Clear the remote/EMS stop command, then restart if required.
  3. Contact Inversol if shutdown was not commanded and the fault returns.
F23 6 Tz_GFCI_OC_Fault Instant AC leakage overcurrent fault
Field checks
  1. Check PV-side cable earthing.
  2. Restart the system 2–3 times.
  3. Contact Inversol if the fault does not clear.
F24 7 DC_Insulation_Fault DC insulation impedance fault
Field checks
  1. Check that PV panel-to-inverter connections are solid and correct.
  2. Ensure the inverter PE conductor is connected to earth.
  3. Contact Inversol if the fault persists.
F25 8 AC_Active_Batt_Fault DC back-feed / active storage fault
Field checks
  1. Check energy-storage DC polarity and that back-feed protection / settings match the site topology.
  2. Confirm storage contactors and BMS allow charge/discharge as configured.
  3. Contact Inversol if the fault returns after a clean power cycle.
F26 9 BusUnbalance_Fault DC bus unbalance fault
Field checks
  1. Wait a short time and check whether values return to normal.
  2. Large inter-phase load imbalance can trigger F26.
  3. DC leakage current can also trigger F26.
  4. Restart the system 2–3 times.
  5. Contact Inversol if the fault does not clear.
F27 10 DC_Insulation_Fault DC insulation impedance fault
Field checks
  1. Same insulation hunt as F2: megger strings, dry connectors, PE integrity.
  2. High humidity mornings can trip — retest when dry before condemning hardware.
  3. Contact Inversol if the fault returns after a clean power cycle.
F28 11 DCIOver_M1_Fault Inverter 1 DC component high fault
Field checks
  1. Check grid CT / sensor path for inverter 1 and look for DC offset on AC current.
  2. Verify load balance and that sensors are seated; escalate if offset stays high.
  3. Contact Inversol if the fault returns after a clean power cycle.
F29 12 Parallel_CANBus_Fault Parallel CAN bus communication fault
Field checks
  1. In parallel mode, check communication cables and inverter addresses.
  2. During parallel startup, units may report F29 until all go ON — then it clears.
  3. If the problem persists, contact Inversol.
F30 13 AC_MainContactor_Fault AC main line contactor fault
F31 14 AC_SlaveContactor_Fault AC auxiliary contactor fault
Field checks
  1. Field-check the auxiliary contactor like F12; confirm interlock wiring to the main contactor.
  2. Contact Inversol if the fault returns after a clean power cycle.
F32 15 DCIOver_M2_Fault Inverter 2 DC component high fault
Field checks
  1. Same DC-component hunt as F28 but on inverter / channel 2 sensors.
  2. In parallel plants, compare readings between Master and Slave.
  3. Contact Inversol if the fault returns after a clean power cycle.
F33 0 AC_OverCurr_Fault AC overcurrent fault
Field checks
  1. Shed non-critical Load / Grid loads; confirm UPS and common loads are within rating.
  2. Look for a short or motor inrush on the protected bus.
  3. Contact Inversol if the fault returns after a clean power cycle.
F34 1 AC_Overlooad_Fault AC overload fault
Field checks
  1. Check connected emergency loads and ensure they are within the power range.
  2. Contact Inversol if the problem does not clear.
F35 2 AC_NoUtility_Fault No utility / grid voltage at AC terminals
Field checks
  1. Measure GRID terminal voltage; confirm upstream breaker / isolator is closed.
  2. If off-grid is intentional, check mode settings so the unit is not waiting for utility.
  3. Contact Inversol if the fault returns after a clean power cycle.
F36 3 AC_GridPhaseSeque_Fault AC grid phase sequence fault
Field checks
  1. Correct phase rotation on GRID (swap two phases) — same field fix as W3.
  2. Re-check after correction before enabling export.
  3. Contact Inversol if the fault returns after a clean power cycle.
F37 4 AC_Volt_Unbalance_Fault AC voltage unbalance
Field checks
  1. Measure phase-to-phase and phase-to-neutral voltages; look for a lost phase or heavy single-phase load.
  2. Correct site imbalance before blaming the inverter.
  3. Contact Inversol if the fault returns after a clean power cycle.
F38 5 AC_Curr_Unbalance_Fault AC three-phase current unbalance
Field checks
  1. Three-phase current unbalance — rebalance site loads across L1/L2/L3; check CT wiring per phase.
  2. FLEX asymmetry is allowed within rating — still find extreme single-phase hogging.
  3. Contact Inversol if the fault returns after a clean power cycle.
F39 6 DCLLC_Over_Current DC-LLC hardware overcurrent
Field checks
  1. Reduce DC-side stress (PV current / storage power); inspect LLC / DC hardware path for shorts.
  2. Do not keep hard-restarting into hardware overcurrent.
  3. Contact Inversol if the fault returns after a clean power cycle.
F40 7 INT_DC_OverCurr_Fault Internal DC overcurrent fault
Field checks
  1. Internal DC overcurrent — check storage and PV currents, then escalate if it repeats without overload.
  2. Capture logs / screenshot at the moment of trip.
  3. Contact Inversol if the fault returns after a clean power cycle.
F41 8 Parallel_System_Stop Parallel system stop
Field checks
  1. Check the status of all hybrid inverters in the cluster (master / slave) — if one unit stops or drops offline, the others often report F41.
  2. Inspect parallel communication cables and that every unit is powered and in the expected mode.
  3. If the problem persists, contact Inversol.
F42 9 Parallel_Version_Fault Parallel firmware mismatch or master/slave link lost
Field checks
  1. Confirm both (all) units in the parallel pair/cluster are powered and online — master and slave.
  2. Check parallel communication cable, connectors, and addresses; a lost link looks like one unit “left” the parallel mode.
  3. Compare firmware versions on every unit in the parallel group — they must match (system name: Parallel_Version_Fault).
  4. Restart the cluster in the correct order after fixing power/comms; if F42 returns, contact Inversol with model, SN, and FW of each unit.
F43 10 AC_VW_OverVolt_Fault AC V-W line overvoltage
Field checks
  1. Measure V–W line voltage vs grid standard limits; check AC cable tightness.
  2. If grid is high, coordinate with the utility / export limits before changing setpoints.
  3. Contact Inversol if the fault returns after a clean power cycle.
F44 11 AC_VW_UnderVolt_Fault AC V-W line undervoltage
Field checks
  1. Measure V–W undervoltage: loose AC joints, long thin cable, or a soft grid.
  2. Confirm breakers are fully closed and voltage recovers under light load.
  3. Contact Inversol if the fault returns after a clean power cycle.
F45 12 AC_UV_OverVolt_Fault AC U-V line overvoltage
Field checks
  1. Same overvoltage field check as F43, but on the U–V line pair.
  2. Compare all three line voltages — one high pair often means a site issue.
  3. Contact Inversol if the fault returns after a clean power cycle.
F46 13 AC_VW_UnderVolt_Fault AC V-W line undervoltage
Field checks
  1. Line undervoltage (V–W on LV map / U–V on HV map): measure the reported pair, tighten AC joints, check cable section.
  2. Confirm family on the nameplate so you diagnose the correct pair.
  3. Contact Inversol if the fault returns after a clean power cycle.
F47 14 F47AC_OverFreq_Fault AC over-frequency fault
Field checks
  1. Check that grid frequency is within specification.
  2. Check AC cables and their connections.
  3. Contact Inversol if the problem repeats.
F48 15 AC_UnderFreq_Fault AC under-frequency fault
Field checks
  1. Check that grid frequency is within specification.
  2. Check AC cables and their connections.
  3. Contact Inversol if the problem repeats.
F49 0 AC_U_GridCurr_DcHigh_Fault Phase U grid current DC component high
Field checks
  1. Phase U grid current has a high DC component — check CT/sensor for that phase and look for asymmetric load or sensor fault.
  2. Escalate if offset remains with balanced load.
  3. Contact Inversol if the fault returns after a clean power cycle.
F50 1 AC_V_GridCurr_DcHigh_Fault Phase V grid current DC component high
Field checks
  1. Same DC-component check as F49 on phase V.
  2. Compare U/V/W sensor readings for one bad channel.
  3. Contact Inversol if the fault returns after a clean power cycle.
F51 2 Battery_TempHigh Energy storage temperature high
F52 3 AC_A_InductCurr_DcHigh_Fault AC inductor phase A DC component high
F53 4 AC_B_InductCurr_DcHigh_Fault AC inductor phase B DC component high
Field checks
  1. Same inductor DC-component check as F52 on phase B.
  2. Contact Inversol if the fault returns after a clean power cycle.
F54 5 BAT_VoltHigh_Fault Energy storage voltage too high
Field checks
  1. Energy-storage voltage high (BAT / BAT2 depending on family): check SOC, charge limits, and that modules are balanced.
  2. Stop charge; verify BMS reports plausible pack voltage.
  3. Contact Inversol if the fault returns after a clean power cycle.
F55 6 DC_VoltHigh_Fault DC bus voltage too high
Field checks
  1. Check that energy-storage voltage is not too high.
  2. Check PV input voltage and ensure it is within the allowed range.
  3. Contact Inversol if the fault does not clear.
F56 7 DC_VoltLow_Fault DC bus voltage too low
F57 8 AC_BackFeed_Fault AC back-feed fault
Field checks
  1. AC back-feed detected — check export settings, meter/CT direction, and that Grid/Load wiring matches the port map.
  2. Do not defeat anti-islanding / back-feed protection.
  3. Contact Inversol if the fault returns after a clean power cycle.
F58 9 BMS_Communication_Fault BMS communication fault
Field checks
  1. Check energy-storage voltage.
  2. If it is too low, charge from PV or from the grid.
  3. Contact Inversol if the fault does not clear.
F59 10 AC_V_GridCurr_High_Fault Phase V grid current overcurrent
Field checks
  1. Phase V grid current overcurrent — shed load on that phase; check CT rating and short circuits on phase V.
  2. Contact Inversol if the fault returns after a clean power cycle.
F60 11 Gen_Volt_or_Fre_Fault Generator voltage or frequency fault
Field checks
  1. Measure generator voltage and frequency at Gen port; confirm GEN Switch / ATS sequencing.
  2. Warm up the genset before connecting; check Gen settings in the menu.
  3. Contact Inversol if the fault returns after a clean power cycle.
F61 12 Button_Manual_OFF Manual OFF button pressed
Field checks
  1. Confirm the unit was intentionally stopped (HMI / remote / OFF button) — clear the stop command and restart if required.
  2. If nobody commanded OFF, check EMS / dry-contact stop wiring.
  3. Contact Inversol if the fault returns after a clean power cycle.
F62 13 DRMs0_Stop DRM stop (DRMs0)
Field checks
  1. DRM applies to the Australian market only.
  2. Check whether the DRM function is active in settings.
  3. Contact Inversol if the problem repeats after a restart.
F63 14 Arc_Fault Arc fault
Field checks
  1. ARC detection applies to the USA market only.
  2. Check PV module cable connections and clear the fault.
  3. Contact Inversol if the problem repeats.
F64 15 Heatsink_HighTemp_Fault Heatsink over-temperature fault

Need install / CT / floating-neutral context? Start with INVERSOL FLEX.

Deye W/F codes →

Buyer and EMS briefs that pair with EcoBSS FLEX fault pages — code detail stays on Academy.