Warning 3P LV W4

meter_Comm_Fail

Energy meter communication failure

Academy field checklist (meter_Comm_Fail) — no EcoBSS service-table row for this bit.

Register map

Family
Three-phase LV (FLEX 3L)
Register
553
Bit
3

Field checks

  1. Check RS485 / meter wiring, baud rate, and Modbus address vs the external meter (e.g. Eastron).
  2. Confirm CT orientation and that the meter is powered.
  3. Contact Inversol if the fault returns after a clean power cycle.

FAQ

What does EcoBSS W4 mean?
Energy meter communication failure
What should I check for EcoBSS W4?
  1. Check RS485 / meter wiring, baud rate, and Modbus address vs the external meter (e.g. Eastron).
  2. Confirm CT orientation and that the meter is powered.
  3. Contact Inversol if the fault returns after a clean power cycle.
When should I contact Inversol?
Confirm LV vs HV family on the nameplate, complete the field checks, then contact Inversol with model, SN, family, and a photo if the code returns after a clean power cycle.

Partner lookup from EcoBSS Flex register map V1.2 — not a substitute for the official service manual or live measurements. Always match the inverter family (3P LV / FLEX 3L vs 3P HV).