AIO for Business: Diesel Generator Alternative
Diesel generator alternative in Tbilisi: AIO / LiFePO4 BESS — 10 ms UPS, peak shaving. Request an Inversol audit!
From
3,680₾
HECKMAN RHFP05100A is a modular High-Voltage LiFePO₄ system spanning roughly 204.8–665.6 V DC and 20–65 kWh per configuration—built for series strings on Deye SG01HP3 hybrids, not parallel 51.2 V stacks.
| Parameter | 20 kWh | 25 kWh | 30 kWh | 35 kWh | 40 kWh | 45 kWh | 50 kWh | 55 kWh | 60 kWh | 65 kWh |
|---|---|---|---|---|---|---|---|---|---|---|
| System Configuration | ||||||||||
| Configuration | 1xBMS+4xBAT | 1xBMS+5xBAT | 1xBMS+6xBAT | 1xBMS+7xBAT | 1xBMS+8xBAT | 1xBMS+9xBAT | 1xBMS+10xBAT | 1xBMS+11xBAT | 1xBMS+12xBAT | 1xBMS+13xBAT |
| Nominal Voltage | 204.8 V | 256 V | 307.2 V | 358.4 V | 409.6 V | 460.8 V | 512 V | 563.2 V | 614.4 V | 665.6 V |
| Nominal Capacity | 20.5 kWh | 25.6 kWh | 30.7 kWh | 35.9 kWh | 40.9 kWh | 46.1 kWh | 51.2 kWh | 56.3 kWh | 61.4 kWh | 66.1 kWh |
| BMS Type | RHBMS | RHBMS | RHBMS | RHBMS | RHBMS MAX | RHBMS MAX | RHBMS MAX | RHBMS MAX | RHBMS MAX | RHBMS MAX |
| Max. Charge/Discharge Current | 50A / 50A | |||||||||
| Cycle Life | 6000 cycles (25°C, 0.5C/0.5C, 90% DOD, EOL 70%) | |||||||||
| Module Expansion | Parallel 4–13 modules per 1xBMS; up to 1040 kWh per inverter* | |||||||||
| Communication | CAN/RS485 | |||||||||
| IP Rating | IP21 | |||||||||
| Cooling | Passive | |||||||||
| Short Circuit Protection | Yes | |||||||||
| Discharge Overcurrent Protection | Yes | |||||||||
| Charge Overcurrent Protection | Yes | |||||||||
| Deep Discharge Protection | Yes | |||||||||
| Temperature Protection | Yes | |||||||||
| Single Module (RHFP) | ||||||||||
| Brand | HECKMAN | |||||||||
| Model | RHFP | |||||||||
| Number of Cells | 16S | |||||||||
| Cell Capacity | 100 Ah | |||||||||
| Nominal Capacity | 5.12 kWh | |||||||||
| Usable Capacity | 4.86 kWh | |||||||||
| Nominal Voltage | 51.2 V | |||||||||
| Recommended Charging Current | 30A (0.3C) | |||||||||
| Nominal Charge/Discharge Power | 4.86 kW | |||||||||
| Efficiency | 95% | |||||||||
| Cell Technology | LFP Prismatic | |||||||||
| Cell Grade | Grade A | |||||||||
| Noise Level | 0 dB | |||||||||
| Operating Temperature | -15°C to 60°C | |||||||||
| Charging Temperature | 0°C to 55°C | |||||||||
| Dimensions (W x D x H) | 443 x 410 x 135 mm | |||||||||
| Weight | 45 kg | |||||||||
| Relative Humidity | ≥90% | |||||||||
| Warranty | 10 years | |||||||||
HV modules wire in series to reach the inverter's 200–850+ V window. Each module must be SOC-balanced before connection—unequal voltage causes immediate BMS fault. Master BMS CAN terminates at the HP3 inverter; Slaves never share battery CAN.
Modularity lets EPC teams scale kWh by adding series blocks in OPEN RACK HP or custom enclosures. BOS savings versus LV come from thinner DC conductors and fewer shunt points—critical on 30–80 kW hybrid feeders.
Compatible with Deye SUN-10K / 12K / 15K / 20K (SG01HP3), SUN-30K, SUN-50K, and SUN-80K HV hybrids. Pair with heckman-open-rack for airflow and service access.
Official product documentation and datasheets.
Datasheet (PDF) PDFNearby power classes and matching LiFePO4 from Tbilisi stock — compare before you quote.
Engineering notes that help you size and choose this product.
Diesel generator alternative in Tbilisi: AIO / LiFePO4 BESS — 10 ms UPS, peak shaving. Request an Inversol audit!
Peak shaving for business in Tbilisi: cut Telasi/Energo-Pro demand peaks without a new feeder. Deye + LiFePO4 — request an audit!
HoReCa solar in Georgia under Net-Billing: self-consumption, evening LiFePO4 buffer, UPS <10 ms, Smart Load, Gen port. LV vs HV and install risks. Request a hotel quote.