From

3,680₾

Get a Quote
HECKMAN RHFP05100A HV Battery System (20–65 kWh)
SKU
RHFP05100A
Brand
HECKMAN
Datasheet (PDF)

HECKMAN RHFP05100A HV Battery System (20–65 kWh)

HECKMAN RHFP05100A is a modular High-Voltage LiFePO₄ system spanning roughly 204.8–665.6 V DC and 20–65 kWh per configuration—built for series strings on Deye SG01HP3 hybrids, not parallel 51.2 V stacks.

Tech Specs

HECKMAN RHFP05100A HV Battery System (20–65 kWh) — Tech Specs
Parameter 20 kWh 25 kWh 30 kWh 35 kWh 40 kWh 45 kWh 50 kWh 55 kWh 60 kWh 65 kWh
System Configuration
Configuration 1xBMS+4xBAT 1xBMS+5xBAT 1xBMS+6xBAT 1xBMS+7xBAT 1xBMS+8xBAT 1xBMS+9xBAT 1xBMS+10xBAT 1xBMS+11xBAT 1xBMS+12xBAT 1xBMS+13xBAT
Nominal Voltage 204.8 V 256 V 307.2 V 358.4 V 409.6 V 460.8 V 512 V 563.2 V 614.4 V 665.6 V
Nominal Capacity 20.5 kWh 25.6 kWh 30.7 kWh 35.9 kWh 40.9 kWh 46.1 kWh 51.2 kWh 56.3 kWh 61.4 kWh 66.1 kWh
BMS Type RHBMS RHBMS RHBMS RHBMS RHBMS MAX RHBMS MAX RHBMS MAX RHBMS MAX RHBMS MAX RHBMS MAX
Max. Charge/Discharge Current 50A / 50A
Cycle Life 6000 cycles (25°C, 0.5C/0.5C, 90% DOD, EOL 70%)
Module Expansion Parallel 4–13 modules per 1xBMS; up to 1040 kWh per inverter*
Communication CAN/RS485
IP Rating IP21
Cooling Passive
Short Circuit Protection Yes
Discharge Overcurrent Protection Yes
Charge Overcurrent Protection Yes
Deep Discharge Protection Yes
Temperature Protection Yes
Single Module (RHFP)
Brand HECKMAN
Model RHFP
Number of Cells 16S
Cell Capacity 100 Ah
Nominal Capacity 5.12 kWh
Usable Capacity 4.86 kWh
Nominal Voltage 51.2 V
Recommended Charging Current 30A (0.3C)
Nominal Charge/Discharge Power 4.86 kW
Efficiency 95%
Cell Technology LFP Prismatic
Cell Grade Grade A
Noise Level 0 dB
Operating Temperature -15°C to 60°C
Charging Temperature 0°C to 55°C
Dimensions (W x D x H) 443 x 410 x 135 mm
Weight 45 kg
Relative Humidity ≥90%
Warranty 10 years

HV modules wire in series to reach the inverter's 200–850+ V window. Each module must be SOC-balanced before connection—unequal voltage causes immediate BMS fault. Master BMS CAN terminates at the HP3 inverter; Slaves never share battery CAN.

Modularity lets EPC teams scale kWh by adding series blocks in OPEN RACK HP or custom enclosures. BOS savings versus LV come from thinner DC conductors and fewer shunt points—critical on 30–80 kW hybrid feeders.

Compatible with Deye SUN-10…25K, 30…50K, and 80K HP3 models. Pair with heckman-open-rack for airflow and service access. OASIS cabinets compete at fixed 60 kWh increments.

Ideal for

  • C&I ESS beyond 40 kWh where LV is cost-prohibitive
  • EPC firms standardizing HECKMAN + Deye HP3 in Georgia
  • Sites with long DC runs from battery room to inverter wall

Technical FAQ

Series vs parallel?
Always series for voltage rise—never parallel HV modules like 51.2 V bricks.
SOC balancing procedure?
Pre-charge each module to identical SOC with approved balancer before closing series links—non-negotiable commissioning step.
Voltage range?
Roughly 204.8–665.6 V depending on module count—must remain inside specific HP3 model DC limits.
LV HECKMAN compatibility?
RLFP/WLFP/MLFP are 51.2 V parallel only—electrically incompatible with HP3 inverters.