Deye

Deye warnings & faults

W1–W32 and F1–F64 as shown on Deye hybrid displays / loggers. Partner lookup table — not a field repair manual.

← All brands

System names match the inverter / logger display (English). Descriptions are partner-facing. Firmware maps can differ by model family — treat F7 vs F07 and F8 vs F08 as alternate numbering on some lines.

Error won't clear? Send a photo of the display to WhatsApp +995 568 999 668: an Inversol engineer will tell you what to check.

Most searched codes with Inversol field notes

W Warnings (W1–W32)

Code System name Description
W1 Grid Voltage Warning Grid voltage close to threshold limit
Field checks
  1. Wait 1–5 minutes for automatic recovery of grid parameters.
  2. If it persists, measure grid voltage at the GRID terminals with a multimeter.
  3. Compare readings with the working range set for your grid standard in the menu.
W2 FAN WARN Abnormal cooling fan operation
W3 Grid Phase Wrong Incorrect grid phase sequence
W4 Meter Comm Fail Energy meter communication failure
W5 Upgrade Error Warning Firmware upgrade error warning
W6 PV Voltage Warning PV input voltage close to limit
Field checks
  1. Measure open-circuit voltage (Voc) on the MPPT inputs.
  2. Reduce series modules in the string if Voc exceeds the working limit.
W7 PV Current Warning PV input current close to limit
Field checks
  1. Review the PV array configuration per MPPT.
  2. Ensure string short-circuit current (Isc) does not exceed the max current per MPPT tracker.
W8 DC Bus Voltage Warning DC bus voltage close to limit
W9 AC Current Warning AC current close to threshold limit
Field checks
  1. Reduce power of loads connected to the inverter output.
  2. Eliminate peak overloads (motors / compressors starting together).
W10 Internal Temp Warning High internal temperature warning
Field checks
  1. Clean the heatsink of dust.
  2. Keep ≥30–50 cm free space for ventilation; avoid direct sun on the unit.
W11 Heatsink Temp Warning Elevated heatsink temperature
W12 Hardware Warning General hardware warning
Field checks
  1. Fully restart: disconnect AC, PV and energy storage for 3–5 minutes.
  2. If the warning returns, schedule service-centre diagnostics.
W13 Firmware Version Warning Firmware version mismatch/conflict
W14 Grid Frequency Warning Grid frequency close to limit
W15 Grid Impedance Warning High grid impedance
Field checks
  1. Retorque AC and neutral terminal connections.
  2. Confirm AC feeder cross-section is adequate for the install.
W16 AC Voltage Unbalance Warning AC voltage phase unbalance
Field checks
  1. Redistribute single-phase loads in the distribution board to reduce phase skew.
  2. Check voltage balance on the utility infeed.
W17 AC Current Unbalance Warning AC current phase unbalance
Field checks
  1. Redistribute single-phase loads in the distribution board to reduce phase skew.
  2. Check voltage balance on the utility infeed.
W18 Power Derating Warning Inverter power derating active
Field checks
  1. Check heatsink temperature and grid voltage.
  2. Expect derating when T > ~75 °C or when grid voltage rises — self-protection.
W19 Reactive Power Control Warning Reactive power control active
Field checks
  1. Review reactive-power compensation in Advanced Settings → Reactive Power.
W20 Export Limitation Warning Grid export limitation active
Field checks
  1. Check Zero Export / export-limit settings.
  2. Confirm CT arrow direction matches the installation diagram.
W21 Zero Export Warning Zero-export mode active
Field checks
  1. Check Zero Export / export-limit settings.
  2. Confirm CT arrow direction matches the installation diagram.
W22 DRM Control Warning DRM control active
W23 Remote Control Warning Inverter remotely controlled
Field checks
  1. Check the log of external control commands — the unit may be under EMS / cloud control.
W24 Parallel Sync Warning Parallel system synchronization warning
Field checks
  1. Check integrity of parallel synchronisation cables.
  2. Confirm bus terminator switches (120 Ω) are set correctly.
W25 Parallel Power Limit Warning Parallel system power limit warning
Field checks
  1. Check integrity of parallel synchronisation cables.
  2. Confirm bus terminator switches (120 Ω) are set correctly.
W26 Battery Voltage Warning Energy storage voltage close to limit
Field checks
  1. Measure energy-storage voltage with a multimeter.
  2. Charge the storage or adjust Low Battery protection setpoints.
W27 Battery Temperature Warning Energy storage temperature close to limit
Field checks
  1. Check ventilation in the energy-storage room.
  2. Confirm the temperature sensor is seated correctly on the pack.
W28 BMS Data Abnormal Warning Abnormal BMS data received
Field checks
  1. Verify the selected lithium / BMS protocol (Lithium Mode).
  2. Confirm cell parameters display correctly on the HMI / logger.
W29 Communication Delay Warning Communication bus delay warning
Field checks
  1. Route and shield communication cables away from AC power runs to reduce EMI.
W30 System Load Warning High system load warning
W31 Battery comm warn Energy storage communication warning
W32 Parallel comm warn Parallel communication warning
Field checks
  1. Replace parallel-link patch cords between inverters.
  2. Confirm each unit in the cluster has a unique inverter number.

F Faults (F1–F64)

Code System name Description
F1 DC Inversed Fault Reverse DC (PV) polarity fault
F2 DC Insulation Failure Low DC insulation resistance
Field checks
  1. Measure DC insulation resistance to earth with a megger (target Riso > 1 MΩ).
  2. Find damaged cable or moisture ingress in MC4 connectors.
  3. Do not raise trip thresholds to hide a real earth fault.
F3 GFDI Failure DC ground fault detection (GFDI) error
Field checks
  1. Disconnect PV and restart the inverter.
  2. If it persists, check the earthing loop and leakage-current sensor integrity.
F4 GFDI Ground Failure Ground / GFDI fault
Field checks
  1. Disconnect PV and restart the inverter.
  2. If it persists, check the earthing loop and leakage-current sensor integrity.
F5 EEPROM Read Failure EEPROM memory read failure
Field checks
  1. Reset settings to factory defaults from the HMI menu.
  2. If the fault remains, the control board may need replacement.
F6 EEPROM Write Failure EEPROM memory write failure
Field checks
  1. Reset settings to factory defaults from the HMI menu.
  2. If the fault remains, the control board may need replacement.
F7 DC/DC Softstart Fault DC/DC soft-start failure
Field checks
  1. Check the energy-storage DC connection path and input fuses.
  2. Restart the system after clearing the DC path.
F07 GFDI Fuse Blown Blown GFDI protection fuse
Field checks
  1. De-energise the inverter.
  2. Replace the blown GFDI fuse and clear the primary PV-to-earth fault first.
F8 GFDI Relay Failure GFDI protection relay fault
Field checks
  1. GFDI earth relay fault — power board needs service repair.
F08 GFDI Ground Touch Fault Improper ground contact / Touch fault
Field checks
  1. Verify the protective earth (PE) conductor is firmly bonded to the inverter chassis.
F9 IGBT Failure IGBT power module failure
Field checks
  1. Internal IGBT power-module fault — diagnostics and board-level repair at a service centre.
F10 AuxPowerBoard Failure Auxiliary power supply board failure
F11 / F30 AC MainContactor Fault Main AC contactor failure
Field checks
  1. Inspect and, if needed, replace the main AC power contactor / relay.
F12 / F31 AC SlaveContactor Fault Auxiliary AC contactor failure
Field checks
  1. Auxiliary contactor fault — contact service for replacement.
F13 Grid Mode Changed Grid operational mode changed
F14 DC OverCurr Fault DC overcurrent fault
F15 SW AC OverCurr Fault Software AC overcurrent protection fault
F16 GFCI Leakage Fault AC leakage current exceeding threshold (GFCI)
Field checks
  1. Check connected appliances for chassis leakage.
  2. Verify correct N and PE wiring (do not bypass residual-current protection).
F17 Tz PV OverCurr Fault PV instantaneous overcurrent fault
Field checks
  1. Check PV strings for short circuits.
  2. Confirm module current ratings match the inverter DC input limits.
F18 HW AC OverCurr Fault Hardware-level AC overcurrent fault
F19 Tz Integ Fault Internal inverter integration/MCU fault
Field checks
  1. Internal DSP integration fault — de-energise the inverter for 5 minutes for a full restart.
F20 Tz Dc OverCurr Fault Off-grid DC overcurrent fault
F21 DC Leakage Flow Fault DC leakage current detected
F22 Emergency Stop Fault System emergency shutdown triggered
Field checks
  1. Release the physical E-Stop button or check the emergency connector contacts.
F23 AC Leakage Current Fault Critical AC leakage current fault
Field checks
  1. Check connected appliances for chassis leakage.
  2. Verify correct N and PE wiring (do not bypass residual-current protection).
F24 DC Insulation Impedance Fault Critically low DC insulation impedance
Field checks
  1. Measure DC insulation resistance to earth with a megger (target Riso > 1 MΩ).
  2. Find damaged cable or moisture ingress in MC4 connectors.
F25 DC Feedback Fault DC circuit feedback loop error
F26 DC Busbar Unbalanced Fault DC busbar voltage unbalance
Field checks
  1. Hardware fault in DC measurement circuits or bus capacitors — service repair.
F27 DC End Insulation Fault End-circuit DC insulation breakdown
F28 DCIOver M1/M2 Fault MPPT1 / MPPT2 overcurrent fault
Field checks
  1. Check current distribution across MPPT trackers.
  2. Reduce current on the overloaded MPPT channel.
F29 Parallel CANBus Fault Parallel CAN communication bus fault
F32 DC Channel High Fault Excessively high DC channel voltage
F33 AC OverCurr Fault General AC overcurrent fault
Field checks
  1. Check LOAD and GRID output lines for short circuits.
  2. Disconnect heavy loads and restart the unit.
F34 AC Overload Fault AC power overload fault
F35 AC NoUtility Fault No grid utility voltage detected
F36 AC GridPhaseSeque Fault AC grid phase sequence failure
Field checks
  1. Swap phases L1 and L2 on the GRID terminals.
F37 AC Volt Unbalance Fault Critical AC voltage unbalance fault
F38 Parallel System Stop Parallel system emergency stop
Field checks
  1. Check fault messages on the other inverters in the parallel cluster.
F39 AC Over Current (1 cycle) Instantaneous 1-cycle AC overcurrent
F40 Internal DC Over Current Internal DC overcurrent fault
Field checks
  1. Internal DC short / overcurrent — service repair required.
F41 Parallel System Stop Inverter cluster shutdown
F42 Parallel Version Fault Parallel units firmware mismatch
F43 AC VW OverVolt Fault Line V-W overvoltage fault
Field checks
  1. Measure grid voltage.
  2. Adjust the upper overvoltage trip in Grid Settings if allowed by the utility code.
F44 AC VW UnderVolt Fault Line V-W undervoltage fault
Field checks
  1. Measure grid voltage.
  2. Adjust the lower undervoltage protection trip in Grid Settings if allowed.
F45 AC Line Over Voltage AC grid line overvoltage
Field checks
  1. Measure grid voltage.
  2. Adjust the upper overvoltage trip in Grid Settings if allowed by the utility code.
F46 AC Line Under Voltage AC grid line undervoltage
F47 AC OverFreq Fault AC grid over-frequency fault
Field checks
  1. Measure grid frequency, or set generator shaft speed for 50 Hz if on genset.
F48 AC UnderFreq Fault AC grid under-frequency fault
F49 Phase DC Component OC Phase 1 DC component overcurrent
F50 Phase DC Component OC Phase 2 DC component overcurrent
F51 Phase DC Component OC Phase 3 DC component overcurrent
F52 Grid Relay Fault Grid disconnect relay fault
Field checks
  1. Mechanical sticking or failure of the AC grid relay — replace the relay board.
F53 AC Relay Stuck Fault AC contactor/relay mechanically stuck
Field checks
  1. Mechanical sticking or failure of the AC relay — replace the relay board.
F54 AC Relay Self-Check Failure AC relay self-test failure
F55 DC Voltage Too High Dangerously high DC voltage
F56 DC Bus Voltage Too Low/High DC bus voltage out of operational range
F58 BMS Communication Fault Battery BMS communication failure
F62 DRM Function Stop Inverter shutdown via external DRM signal
F63 PV Overcurrent / Choke Fault PV filter choke / inductor overload
F64 High Heatsink Temperature Critical heatsink / IGBT over-temperature
Field checks
  1. Allow the inverter to cool.
  2. Check cooling fans and clean heatsink fins.

Need install / CT / floating-neutral context? Start with INVERSOL FLEX.