Skip to content
Deye SUN-12K-SG01HP3-EU-AM2 Hybrid Inverter
SKU
SUN-12K-SG01HP3-EU-AM2
Brand
Deye
Datasheet (PDF)

Deye SUN-12K-SG01HP3-EU-AM2 Hybrid Inverter

The Deye SUN-12K-SG01HP3-EU-AM2 is a High-Voltage (200–850+ V) commercial hybrid for 12 kW AC — a mid-step HV unit for shops and light industry that need three-phase storage without jumping to 20–30 kW frames.

Tech Specs

Deye SUN-12K-SG01HP3-EU-AM2 Hybrid Inverter — Tech Specs
Parameter SUN-12K-SG01HP3-EU-AM2
Battery Input Data
Battery Type LiFePO4
Battery Voltage Range (V) 160-700
Max. Charging/Discharging Current (A) 37
Charging Strategy for Li-ion Battery Self-adaption to BMS
Number of Battery Input 1
PV String Input Data
Max. PV Access Power (W) 24000
Max. PV Input Power (W) 19200
Max. PV Input Voltage (V) 1000
Start-up Voltage (V) 180
MPPT Voltage Range (V) 150-850
Rated PV Input Voltage (V) 600
Max. Operating PV Input Current (A) 26+20
Max. Input Short-Circuit Current (A) 39+30
No. of MPP Trackers / No. of Strings per MPP Tracker 2/2+1
AC Input/Output Data
Rated AC Input/Output Active Power (W) 12000
Max. AC Input/Output Apparent Power (VA) 13200
Rated AC Input/Output Current (A) 18.2/17.4
Max. AC Input/Output Current (A) 20/19.2
Max. Continuous AC Passthrough (grid to load) (A) 80
Peak Power (off-grid) (W) 1.5 times of rated power,10s
Power Factor Adjustment Range 0.8 leading to 0.8 lagging
Rated Input/Output Voltage 220/380V,230/400V 0.85Un-1.1Un 3L+N+PE
Rated Input/Output Grid Frequency/Range (Hz) 50/45-55, 60/55-65
Total Current Harmonic Distortion THDi <3% (of nominal power)
DC Injection Current <0.5%ln
Efficiency
Max. Efficiency 97.6%
Euro Efficiency 97.0%
MPPT Efficiency >99%
Equipment Protection
Integrated Protections DC Reverse Polarity Protection
AC Output Overcurrent Protection
Thermal Protection
AC Output Overvoltage Protection
AC Output Short Circuit Protection
DC Component Monitoring
Arc Fault Circuit Interrupter (AFCI) (optional)
Anti-islanding Protection
DC Switch
Insulation Impedance Detection
Residual Current Detection
Surge Protection Level TYPE II(DC), TYPE II(AC)
Interface
LCD/LED Display LCD
Communication Interface WiFi, RS485, CAN
Monitor Mode GPRS/WIFI/Bluetooth/4G
General Data
Operating Temperature Range (°C) -40 to +60°C, >45°C Derating
Permissible Ambient Humidity 0-100%
Permissible Altitude 2000 m
Noise (dB) ≤ 55
Ingress Protection (IP) Rating IP 65
Inverter Topology Non-Isolated
Over Voltage Category OVC II(DC), OVC III(AC)
Cabinet Size (W×H×D mm) 408×638×237 (Excluding Connectors and Brackets)
Weight (kg) 30.5
Type of Cooling Intelligent Air Cooling
Grid Regulation IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002,
OVE-Richtlinie R25, G99, VDE-AR-N 4105
Safety / EMC Standard IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2
Key Features (datasheet)
Max. Parallel Units (on-grid and off-grid) 10
Battery Charge/Discharge Time Periods 6

Source: official Deye datasheet for SUN-5/6/8/10/12/15/20/25K-SG01HP3-EU-AM2; values are shown for this model.

Above roughly 20–30 kW of continuous power, 51.2 V architectures begin to punish installers: DC currents climb, mandating 35–50 mm² runs, heavy combiner boxes, and measurable I²R losses on every meter of cable. The 200–850+ V HV bus inverts that equation. A 25 kW charge/discharge profile on HV uses dramatically slimmer conductors and fewer parallel strings, directly cutting Balance of System (BOS) cost before a single kWh is stored.

Energy storage integration follows strict HV rules. Modules such as Heckman RHFP05100A (20–65 kWh scalable racks) or HECKMAN HV RHFP cabinets are wired in series—not parallel stacks of 51.2 V blocks. Every module must be pre-balanced to an identical State of Charge (SOC) before stringing; otherwise the Master BMS will lock out the string. CAN communication from the energy storage Master terminates at the inverter BMS port; grid-side metering typically uses CHINT DTSU 666 on short runs, or Eastron SDM Modbus V2 via RS485/PLC when the measurement point exceeds 30 m.

For Georgian B2B operators facing the 0.35 ₾/kWh tariff, this platform supports peak shaving, time-of-use arbitrage, and unbalanced three-phase loading across commercial feeders. Up to 10 inverters can be paralleled on the SG01HP3 architecture (Master/Slave CAN), scaling toward 250 kW while preserving a single energy storage communication hierarchy. AC Coupling via the GEN port remains available for retrofit sites upgrading legacy On-Grid PV without ripping existing string inverters.

Ideal for

  • ✓ Commercial buildings stepping from LV hybrid into HV without jumping straight to 50 kW hardware
  • ✓ Installers who need RHFP storage between ~20 kWh and 130 kWh on a single HV string
  • ✓ Facilities with long DC cable routes where 51.2 V voltage drop would waste storage ROI

Technical FAQ

At what project size does HV beat 51.2 V LV economics?
There is no single kW threshold, but above ~20–30 kW inverter power or ~40 kWh stored energy, HV cabling and combiner savings usually outweigh the premium on HV modules. The SUN-12K HP3 targets that transition zone before deploying SUN-30K / SUN-50K or SUN-80K units.
Which energy storage systems are approved for this inverter?
Only High-Voltage racks operating within the inverter's 200–850+ V DC window—typically Heckman RHFP05100A strings and HECKMAN RHFP HV racks. Standard 51.2 V HECKMAN or ECOBSS STORE modules are electrically incompatible.
How is grid metering handled on large commercial switchboards?
Factory default integrates CHINT DTSU 666 CT metering. When the utility measurement point is remote (>30 m), specify Eastron SDM Modbus V2 with RS485 or PLC converters on phase conductors—identical philosophy to LV hybrids, but with HV DC safety procedures on the energy storage side.
Can this unit parallel with other SG01HP3 inverters?
Yes. Up to 10 units can be daisy-chained via Parallel CAN. Energy storage BMS CAN connects to the Master inverter only; Slaves receive sequential Modbus IDs. Plan busbar and AC breaker sizing for summed nameplate current.
← Back to catalog: Inverters

Field notes from Inversol Academy for the codes you are most likely to meet with this equipment.

All Deye error codes →

Nearby power classes and matching LiFePO4 from Tbilisi stock — compare before you quote.

Engineering notes that help you size and choose this product.